NMAKSG input / output reactor
NMAKSG (also available with model NMACL as input and NMOCL as output) series of dry iron core series reactors are used for inverter input and output side terminals, connected in series with the inverter. When there are a large number of harmonic sources such as rectification and converter devices in the low-voltage network. At the time, the high harmonics generated by it will seriously endanger the safe operation of the main transformer and other electrical equipment. When the reactor is connected to the inverter, it can effectively absorb the harmonics of the power grid, reduce the leakage current caused by the input high harmonics, reduce the noise and eddy current loss of the motor, smooth filter, reduce the transient voltage dv/dt, and extend the motor. life.
contact number
Product Details

Use and scope of application

NMAKSG (also available with model NMACL as input and NMOCL as output) series of dry iron core series reactors are used for inverter input and output side terminals, connected in series with the inverter. When there are a large number of harmonic sources such as rectification and converter devices in the low-voltage network. At the time, the high harmonics generated by it will seriously endanger the safe operation of the main transformer and other electrical equipment. When the reactor is connected to the inverter, it can effectively absorb the harmonics of the power grid, reduce the leakage current caused by the input high harmonics, reduce the noise and eddy current loss of the motor, smooth filter, reduce the transient voltage dv/dt, and extend the motor. life.


Model meaning

1552266272107144.jpg


Performance parameter

1) Applicable to any brand inverter

2) Voltage drop: input is 5V, output is 9V

3) Rated insulation level 5kV/min

4) Temperature rise limit of each part of the resistance: the core does not exceed 85K, and the temperature rise of the wire does not exceed 95K

5) Reactor noise is not more than 45dB

6) Reactor can store power frequency plus harmonic current is not more than 1.85 times rated current for long-term operation

7) Reactance value linearity: the ratio of the reactance value at 1.8 times the rated current to the reactance value at the rated current is not less than 0.95

8) The difference between any two-phase reactance values of the three-phase reactor is not more than 3% of the soil

Note: Specific performance parameters can be customized.


Parameters Table

5-3.jpg